I was looking at our demands if we tried to source most of our heating load by Solar, it would not be logical to size a system for our worst case situation:

Average winter btu load after insulation infiltration issues addressed 300,000btu


Storage required – 14 hours


BTU Production per sq ft of collector per day, average:


Winter 1,000
Summer 2,000


Storage required to get through average winter night 14x300,000 = 4,200,000


Storage per million btu’s = 2,000 gallons


Total storage required 8,500 gallons


Solar sq footage required about 6,000


Back up required for harsh weather low solar production


By comparison I worked out we would only need 200 sq ft to provide most of our hot water in the summer.